Description
- For general information concerning the operation of a hidrobloc control valve, please consult our general manual (series K).
- Extensive range including two different design
– XG design
– Large flow capacity
– Low head loss
– Watertight at zero flow rate
– XGS design
– Particularly suitable for pressure reduction
– Better cavitation resistance
– Watertight at zero flow rate
Construction
- Sef-lubricated doble guided mobile unit
- Ductile iron body and bonnet
- Stainless steel seat for standard version until DN 400 XG design and DN 600 XGS design
- Powder epoxy coating
- Stainless steel bolting
- Pilot circuit strainer with screen in stainless steel
- Individually packed
Easy Operation and Maintenance
- Visual position indicator with manual drain
- Including isolating valve (s) for pressure gauges
- Equipped with opening speed controller “RO” (DN50 to 300 XG design and DN150 to 499 XGS design only)
- Chamber isolating valve independent from the adjustment of the speed controller
- Maintenance without disassembly from the pipeline
- Easy dismantling fro the top
- Drain plug (stainless steel)
Product according to standard EN 1074-S
Technical Data
- Range DN 50 for XG Design
- PN 25
- Maximum temperature +1°C to +65°C
- Seating class A according to standard ISO 5208-2
- Face to face dimension according to standard EN 558-1 series 1 (except DN1000) and ISO 5752 series 1 (except DN1000)
- Flange drilling according to standard EN 1092-2 and ISO 7005-2; ISO PN 10, 16 or 25 for DN 50 to 1000 (other drillings please consults us)
- Fluid: drinking water or 2 mm fitered untreated water
- Working pressure : 25 bar
- Vertical & Horizontal installation
- The valve body of PN 16 and PN 25 are the same, the difference on flange drilling and pilot circuit
Specifications
- XG : design
– B : 265 mm
– C : 302 mm
– D : 120 mm
– Weight : 35.6 kg